3-Phase Power Supply, Primary Switch Mode for Universal Use – QUINT 48 V DC/10 A
General Data
CB B
Insulation voltage:
Approval package
Electrical equipment of machines
Input/output
Input/PE
Output/PE
3 kV AC (type test)/1.5 kV AC (routine test)
1.5 kV AC (type test)/1.25 kV AC (routine test)
1.25 kV AC (type test)/1.25 kV AC (routine test)
Schem
EN 60 204 (Surge Voltage Category III)
Safety transformers for switched-mode power supply units
Electrical safety
(of IT equipment)
Industrial control equipment
Equipping high voltage installations
with electronic equipment
Safety extra-low voltage
Safe isolation
Protection against electric shock
Protection against dangerous shock currents,
basic requirements for safe isolation
in electrical equipment
Limitation of harmonic line currents
Mounting position
Degree of protection
Class of protection
MTBF
Housing version
Dimensions (W x H x D) + DIN rail
Weight
Climatic Data
EN 61 558-2-17
EN 60950/VDE 0805,
UL/C-UL Recognized UL 60 950 u 1)
U
UL/C-UL Listed UL 508 LISTED 1)
EN 50 178 (VDE 0160)
PELV (EN 60 204)
SELV (EN 60 950)
VDE 0100-410
DIN 57100-410
DIN VDE 0106-101
According to EN 61000-3-2
On horizontal NS 35 DIN rail according to EN 50022
IP 20
Ι , with PE connection
> 500 000 h according to IEC 1709 (SN 29 500)
AluNox (AlMg1), closed
Default upon delivery: Rotated 90°:
(160 x 130 x 125 mm [6.299 x 5.118 x 4.921 in.])(122 x 130 x 163
mm [4.803 x 5.118 x 6.417 in.])
Ambient temperature
Operation
-25°C to +70°C (-13°F to +158°F) (> +60°C [+140°F] derating)
Humidity
Storage
-40°C to +85°C (-40°F to +185°F)
Up to 95% at +25°C (+77°F), no condensation
Vibration
Shock
according to IEC 68-2-6
according to IEC 68-2-27
< 15 Hz, amplitude ±2.5 mm/15 Hz - 150 Hz, 2.3 g, 90 minutes
in resonant frequency
30 g all space directions
UL approval for AC input voltage and ambient temperature up to
Degree of pollution
Climatic category
c
Conforms to the EMC Directive 89/336/EEC and the
Low Voltage Directive 73/23/EEC
2 (according to EN 50 178)
3K3 (according to EN 60 721)
1)
+70°C (+158°F)
EMC (Electromagnetic Compatibility)
Noise Immunity According to EN 61000-6-2:
Requirements
EN 61 000-6-2
QUINT-PS-3x400-500AC/48DC/
10
Electrostatic discharge
EN 61000-4-2 3)
Housing
Level 4
(ESD)
Contact discharge:
Air discharge:
4 kV
8 kV
8 kV
15 kV
Electromagnetic
EN 61000-4-3 2)
Housing
Level 3
HF ? eld
Frequency:
Field strength:
80 - 1000 MHz
10 V/m
80 - 1000 MHz
10 V/m
Fast transients
(burst)
Surge current loads
Conducted
interference
EN 61000-4-4 3)
EN 61000-4-5 3)
EN 61000-4-6 2)
Input:
Output:
Signal:
Input:
Output:
Signal:
I/O/S:
Frequency:
2 kV
2 kV
1 kV
2 kV
1 kV
0.5 kV
0.5 kV
1 kV
0.15 - 80 MHz
asymmetrical 5)
asymmetrical 5)
asymmetrical 5)
asymmetrical 5)
symmetrical 4)
asymmetrical 5)
symmetrical 4)
asymmetrical 5)
asymmetrical 5)
4 kV (Level 4)
2 kV (Level 3)
1 kV (Level 2)
4 kV (Level 4)
2 kV (Level 4)
0.5 kV (Level 1)
0.5 kV (Level 1)
1 kV (Level 2)
Level 3
0.15 - 80 MHz
U 0 :
10 V
10 V
Voltage dips
EN 61000-4-11 3)
Input:
30% reduction of the input
See input data:
voltage for 0.5 periods
Mains buffering
> 20 ms
Noise Emission According to EN 50081-2:
Class A
Radio interference
Radio interference
EN 55011
EN 55011
Class A 6)
6)
EN 55011 (EN 55022) Class B 7)
EN 55011 (EN 55022) Class B 7)
EN 55011 corresponds to CISPR11/EN 55022 corresponds to CISPR22
Criterion A: Normal operating characteristics within the speci ? ed
EN 61000 corresponds to IEC 1000
2)
4)
5)
symmetrical: Cable to cable
asymmetrical: Cable to ground
3)
limits.
Criterion B: Temporary adverse effects on the operating
characteristics that the device corrects independently.
6)
7)
Class A:
Class B:
Industrial application
Industrial and domestic applications
PHOENIX CONTACT page 3 of 10